{"id":2209,"date":"2026-10-08T22:36:04","date_gmt":"2026-10-08T14:36:04","guid":{"rendered":"https:\/\/jutrion.com\/?p=2209"},"modified":"2026-10-08T22:36:07","modified_gmt":"2026-10-08T14:36:07","slug":"275v-vs-320v-vs-385v-spd-choose-correct-uc","status":"publish","type":"post","link":"https:\/\/jutrion.com\/es\/275v-vs-320v-vs-385v-spd-choose-correct-uc\/","title":{"rendered":"275 V vs 320 V vs 385 V SPD: C\u00f3mo Elegir el Uc Correcto"},"content":{"rendered":"<h2 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-large-font-size wp-elements-1\">275 V, 320 V o 385 V: La respuesta corta<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Para una instalaci\u00f3n de 230\/400 V AC, un SPD de 275 V es a menudo el primer candidato cuando su modo de protecci\u00f3n normalmente ve alrededor de 230 V, pero no es una elecci\u00f3n autom\u00e1tica para cada red. Utilice 320 V cuando el dise\u00f1o aprobado necesite m\u00e1s margen de voltaje continuo o sobrevoltaje temporal, y utilice 385 V solo cuando el modo de protecci\u00f3n real, la disposici\u00f3n de puesta a tierra y los datos del fabricante justifiquen esa clasificaci\u00f3n m\u00e1s alta. No seleccione solo en funci\u00f3n del voltaje nominal del sistema.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">El U correcto<sub>c<\/sub> es el voltaje m\u00e1ximo continuo de operaci\u00f3n aprobado m\u00e1s bajo que permanece por encima del voltaje m\u00e1s alto que el SPD puede experimentar continuamente en su modo conectado. Tambi\u00e9n debe sobrevivir a las condiciones de sobrevoltaje temporal esperadas en ese punto. Despu\u00e9s de seleccionar U<sub>c<\/sub>, verifique que el nivel de protecci\u00f3n de voltaje resultante U<sub>p<\/sub> siga siendo lo suficientemente bajo para el equipo protegido.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Esa \u00faltima verificaci\u00f3n es importante porque U<sub>c<\/sub> no es una clasificaci\u00f3n de corriente de sobretensi\u00f3n. Un cartucho de 385 V no es una versi\u00f3n m\u00e1s fuerte de un cartucho de 275 V en todos los aspectos. Puede tolerar un voltaje de frecuencia de potencia sostenido m\u00e1s alto, pero puede comenzar a limitarse a un voltaje m\u00e1s alto y puede tener un U<sub>p<\/sub>. declarado m\u00e1s alto. Por lo tanto, la mejor elecci\u00f3n equilibra la estabilidad del servicio con el nivel de protecci\u00f3n.<\/p>\n\n\n\n<figure class=\"wp-block-image size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"1024\" height=\"341\" src=\"https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/01-spd-uc-275v-320v-385v-comparison-1024x341.webp\" alt=\"\" class=\"wp-image-2231\" srcset=\"https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/01-spd-uc-275v-320v-385v-comparison-1024x341.webp 1024w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/01-spd-uc-275v-320v-385v-comparison-300x100.webp 300w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/01-spd-uc-275v-320v-385v-comparison-768x256.webp 768w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/01-spd-uc-275v-320v-385v-comparison-18x6.webp 18w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/01-spd-uc-275v-320v-385v-comparison.webp 1200w\" sizes=\"auto, (max-width: 1024px) 100vw, 1024px\" \/><figcaption class=\"wp-element-caption\"><code><em>Comparaci\u00f3n de las clasificaciones Uc de SPD de 275 V, 320 V y 385 V en un circuito de 230 V de l\u00ednea a neutro.<\/em><\/code><\/figcaption><\/figure>\n\n\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<h2 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-large-font-size wp-elements-2\">Lo que U<sub>c<\/sub> realmente significa en un SPD AC<\/h2>\n<\/blockquote>\n\n\n\n<p class=\"wp-block-paragraph\">U<sub>c<\/sub> es el voltaje m\u00e1ximo continuo de operaci\u00f3n que puede aplicarse a trav\u00e9s de los terminales del SPD bajo las condiciones declaradas por el fabricante. En un producto AC, normalmente es un valor RMS a la frecuencia declarada. Durante la operaci\u00f3n normal, el SPD debe permanecer estable a este voltaje sin comportarse como si cada cresta de la red fuera una sobretensi\u00f3n.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Esta definici\u00f3n explica por qu\u00e9 U<sub>c<\/sub> debe leerse en un modo de protecci\u00f3n espec\u00edfico:<\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li><strong>L\u2013N:<\/strong> fase a neutro;<\/li>\n\n\n\n<li><strong>L\u2013PE:<\/strong> fase a tierra de protecci\u00f3n;<\/li>\n\n\n\n<li><strong>N\u2013PE:<\/strong> neutro a tierra de protecci\u00f3n; o<\/li>\n\n\n\n<li><strong>L\u2013L:<\/strong> fase a fase en un arreglo dise\u00f1ado para ese modo.<\/li>\n<\/ul>\n\n\n\n<p class=\"wp-block-paragraph\">Una red trif\u00e1sica puede describirse como 230\/400 V, sin embargo, el voltaje a trav\u00e9s de un m\u00f3dulo SPD individual puede ser de 230 V o 400 V dependiendo de d\u00f3nde est\u00e9 conectado ese m\u00f3dulo. Por lo tanto, la etiqueta del sistema y la etiqueta del cartucho no son intercambiables.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">No confunda U<sub>c<\/sub> con las otras cifras impresas en un SPD:<\/p>\n\n\n\n<figure class=\"wp-block-table jutrion-table\"><table class=\"has-fixed-layout\"><thead><tr><th>Marcado<\/th><th>Lo que describe<\/th><th>Lo que no prueba<\/th><\/tr><\/thead><tbody><tr><td>U<sub>c<\/sub><\/td><td>Voltaje m\u00e1ximo que puede permanecer continuamente a trav\u00e9s del modo de protecci\u00f3n declarado<\/td><td>Capacidad de descarga de sobretensi\u00f3n o el voltaje entregado a la carga durante una sobretensi\u00f3n<\/td><\/tr><tr><td>U<sub>p<\/sub><\/td><td>Nivel de protecci\u00f3n de voltaje declarado bajo condiciones de prueba de impulso especificadas<\/td><td>Tolerancia de voltaje de operaci\u00f3n continua<\/td><\/tr><tr><td>I<sub>n<\/sub><\/td><td>Deber de corriente de descarga nominal utilizando la forma de onda 8\/20 \u00b5s<\/td><td>Capacidad de rayo directo<\/td><\/tr><tr><td>I<sub>m\u00e1x<\/sub><\/td><td>Corriente de descarga m\u00e1xima para un SPD de Tipo 2 bajo la prueba de 8\/20 \u00b5s declarada<\/td><td>Deber repetido a ese valor m\u00e1ximo<\/td><\/tr><tr><td>I<sub>imp<\/sub><\/td><td>Deber de corriente de impulso asociado con pruebas de Tipo 1 y la forma de onda 10\/350 \u00b5s<\/td><td>Un sustituto para U<sub>c<\/sub> o U<sub>p<\/sub><\/td><\/tr><tr><td>U<sub>T<\/sub> \/ datos TOV<\/td><td>Comportamiento bajo un sobrevoltaje temporal de frecuencia de potencia especificado durante una duraci\u00f3n determinada<\/td><td>Permiso para operar continuamente a ese voltaje<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">Para una explicaci\u00f3n m\u00e1s amplia sobre los tipos de SPD, las clasificaciones de corriente de descarga y las posiciones de instalaci\u00f3n, utilice el <a href=\"https:\/\/jutrion.com\/es\/surge-protective-device-guide\/\">gu\u00eda de dispositivos de protecci\u00f3n contra sobretensiones de JUTRION<\/a>. Este art\u00edculo se centra en la decisi\u00f3n m\u00e1s espec\u00edfica: elegir entre los valores de U<sub>c<\/sub> de 275 V, 320 V y 385 V.<\/p>\n\n\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<h2 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-large-font-size wp-elements-3\">Por qu\u00e9 Aparecen las Tres Clasificaciones en Proyectos de 230\/400 V<\/h2>\n<\/blockquote>\n\n\n\n<p class=\"wp-block-paragraph\">Las tres clasificaciones existen porque un sistema de baja tensi\u00f3n no presenta un voltaje perfectamente fijo bajo todas las condiciones de operaci\u00f3n y falla. La tolerancia de suministro, la regulaci\u00f3n de voltaje, la distorsi\u00f3n arm\u00f3nica, el desplazamiento del neutro, las fallas a tierra y el arreglo de puesta a tierra pueden cambiar el voltaje aplicado a un modo de protecci\u00f3n. Las familias de productos tambi\u00e9n difieren en su comportamiento TOV y tecnolog\u00eda interna.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Para un suministro nominal de 230 V de fase a neutro, la relaci\u00f3n simple es:<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>275 \/ 230 = 1.20, 320 \/ 230 = 1.39, y 385 \/ 230 = 1.67.<\/strong><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Estas proporciones son \u00fatiles para ver el margen de voltaje continuo creciente, pero no son una f\u00f3rmula de selecci\u00f3n completa. No describen el voltaje m\u00e1ximo en estado estacionario del sitio, el modo de protecci\u00f3n, o c\u00f3mo se comporta el SPD durante un TOV. Dos SPDs con el mismo U<sub>c<\/sub> tambi\u00e9n pueden tener diferentes U<sub>T<\/sub>, U<sub>p<\/sub>, datos de protecci\u00f3n de respaldo y desconexi\u00f3n.<\/p>\n\n\n\n<figure class=\"wp-block-table jutrion-table\"><table class=\"has-fixed-layout\"><thead><tr><th>U<sub>c<\/sub> clase<\/th><th>Raz\u00f3n t\u00edpica por la que entra en la lista corta<\/th><th>Principal beneficio<\/th><th>Verificaci\u00f3n principal antes de la aprobaci\u00f3n<\/th><\/tr><\/thead><tbody><tr><td>275 V CA<\/td><td>El modo de protecci\u00f3n normalmente ve aproximadamente 230 V y los datos de TOV del producto se ajustan a la red<\/td><td>Un margen de voltaje m\u00e1s ajustado a menudo soporta un nivel de protecci\u00f3n relativamente bajo<\/td><td>\u00bfPuede permanecer estable en el voltaje continuo m\u00e1s alto del sitio y sobrevivir al TOV especificado?<\/td><\/tr><tr><td>320 V CA<\/td><td>El dise\u00f1o necesita un margen de voltaje operativo adicional, o el fabricante asigna esta clase a la disposici\u00f3n de red requerida<\/td><td>M\u00e1s tolerancia a la elevaci\u00f3n de voltaje sostenida que una clase de 275 V<\/td><td>\u00bfSu U<sub>p<\/sub> sigue coordinado con el voltaje de impulso de resistencia del equipo?<\/td><\/tr><tr><td>385 V CA<\/td><td>El modo conectado o la estrategia de TOV aprobada requieren un margen de voltaje sustancialmente mayor<\/td><td>Riesgo reducido de operaci\u00f3n no deseada por voltaje elevado de frecuencia de potencia<\/td><td>\u00bfDeja la clase m\u00e1s alta un nivel de protecci\u00f3n efectiva suficientemente bajo en la carga?<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">Esta es una tabla de selecci\u00f3n, no un gr\u00e1fico de sustituci\u00f3n universal. Un dispositivo de 320 V no puede reemplazar autom\u00e1ticamente un dispositivo de 275 V, y un dispositivo de 385 V no puede ser aprobado simplemente porque es menos probable que reaccione a un voltaje de red elevado.<\/p>\n\n\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<h2 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-large-font-size wp-elements-4\">Comience con el Voltaje a Trav\u00e9s de Cada Modo de Protecci\u00f3n<\/h2>\n<\/blockquote>\n\n\n\n<p class=\"wp-block-paragraph\">Dibuje la conexi\u00f3n del SPD antes de elegir el cartucho. Marque el voltaje normal a trav\u00e9s de cada modo y pregunte qu\u00e9 voltaje puede aparecer all\u00ed durante los estados operativos y de falla cre\u00edbles definidos por el proyecto.<\/p>\n\n\n\n<h3 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-medium-font-size wp-elements-5\">Protecci\u00f3n Monof\u00e1sica 230 V, L\u2013N<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">Un SPD conectado de l\u00ednea a neutro normalmente ve el voltaje fase-neutro. En un sistema de 230 V ordinario y correctamente regulado, 275 V se incluye com\u00fanmente en la lista corta. La aprobaci\u00f3n a\u00fan depende del rango de suministro permitido, mediciones en el sitio donde sea relevante, requisitos de TOV y la hoja de datos exacta.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Si el sitio opera regularmente cerca o por encima del l\u00edmite superior asumido por el dise\u00f1o, seleccionar 275 V solo por la etiqueta nominal puede causar envejecimiento acelerado o operaci\u00f3n innecesaria del desconector t\u00e9rmico. La respuesta de ingenier\u00eda no es autom\u00e1ticamente \u201cinstalar 385 V.\u201d Primero determine si el voltaje elevado es una condici\u00f3n operativa v\u00e1lida, un problema de calidad de suministro, una falla de neutro o una aplicaci\u00f3n fuera del dise\u00f1o original.<\/p>\n\n\n\n<h3 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-medium-font-size wp-elements-6\">Protecci\u00f3n Trif\u00e1sica 230\/400 V, L\u2013N o L\u2013PE<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">En un sistema en estrella de 230\/400 V, cada fase est\u00e1 aproximadamente a 230 V respecto al neutro y aproximadamente a 400 V respecto a otra fase. Un m\u00f3dulo conectado L\u2013N, por lo tanto, no est\u00e1 expuesto continuamente a 400 V durante la operaci\u00f3n normal. Un m\u00f3dulo conectado en otro modo puede enfrentar un requisito diferente.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Esta distinci\u00f3n es la raz\u00f3n por la que el conteo de polos no selecciona U<sub>c<\/sub>. \u201cEl SPD de cuatro polos para un panel de 400 V\u201d est\u00e1 incompleto. La especificaci\u00f3n debe indicar la configuraci\u00f3n de la red y el circuito de protecci\u00f3n, como 3+1 o 4+0, e identificar el voltaje en cada m\u00f3dulo.<\/p>\n\n\n\n<figure class=\"wp-block-image size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"1024\" height=\"341\" src=\"https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/02-three-phase-spd-3-plus-1-protection-modes-1024x341.webp\" alt=\"\" class=\"wp-image-2232\" srcset=\"https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/02-three-phase-spd-3-plus-1-protection-modes-1024x341.webp 1024w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/02-three-phase-spd-3-plus-1-protection-modes-300x100.webp 300w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/02-three-phase-spd-3-plus-1-protection-modes-768x256.webp 768w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/02-three-phase-spd-3-plus-1-protection-modes-18x6.webp 18w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/02-three-phase-spd-3-plus-1-protection-modes.webp 1200w\" sizes=\"auto, (max-width: 1024px) 100vw, 1024px\" \/><figcaption class=\"wp-element-caption\"><code><em>Disposici\u00f3n de SPD trif\u00e1sico 3+1 con L1, L2 y L3 protegidos a neutro y un m\u00f3dulo N-PE separado.<\/em><\/code><\/figcaption><\/figure>\n\n\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<h2 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-large-font-size wp-elements-7\">Sistema de puesta a tierra y disposici\u00f3n del circuito Cambiar la respuesta<\/h2>\n<\/blockquote>\n\n\n\n<p class=\"wp-block-paragraph\">El mismo suministro nominal de 230\/400 V puede requerir un ensamblaje de SPD diferente dependiendo de si es TN-C, TN-S, TT o IT. La pregunta importante no es solo cu\u00e1ntos m\u00f3dulos est\u00e1n instalados, sino qu\u00e9 componentes est\u00e1n conectados entre qu\u00e9 conductores.<\/p>\n\n\n\n<h3 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-medium-font-size wp-elements-8\">Sistemas TN<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">Los sistemas TN-C y TN-S tienen diferentes puntos de conexi\u00f3n PEN o N\/PE, por lo que se debe utilizar un ensamblaje declarado para la disposici\u00f3n TN espec\u00edfica. Un cartucho de 275 V es com\u00fan para un modo de protecci\u00f3n de 230 V, pero su rendimiento TOV a\u00fan debe pasar; las variantes de 320 V o 385 V se utilizan solo donde el margen de voltaje continuo o TOV requerido lo respalda.<\/p>\n\n\n\n<h3 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-medium-font-size wp-elements-9\">Sistemas TT y circuitos 3+1<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">Una disposici\u00f3n 3+1 coloca com\u00fanmente componentes limitadores de voltaje de fase a neutro y un componente basado en gap de chispa de neutro a PE. Por lo tanto, los cartuchos de fase se seleccionan para el servicio L\u2013N; el componente N\u2013PE tiene datos diferentes. Esta disposici\u00f3n puede controlar las consecuencias de TOV en sistemas TT, pero debe seguir la norma de instalaci\u00f3n aplicable y las instrucciones del fabricante.<\/p>\n\n\n\n<h3 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-medium-font-size wp-elements-10\">Sistemas IT<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">En un sistema IT, los conductores sanos pueden elevarse en relaci\u00f3n a tierra despu\u00e9s de la primera falla a tierra. No especifique un cartucho L\u2013PE de 275 V \u00fanicamente porque las cargas se denominan 230 V. Utilice un ensamblaje declarado para la disposici\u00f3n IT y verifique el voltaje conductor-tierra, los modos de protecci\u00f3n y el comportamiento TOV.<\/p>\n\n\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<h2 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-large-font-size wp-elements-11\">La verdadera compensaci\u00f3n: envejecimiento molesto versus nivel de protecci\u00f3n<\/h2>\n<\/blockquote>\n\n\n\n<p class=\"wp-block-paragraph\">Elegir U<sub>c<\/sub> demasiado bajo y elegirlo demasiado alto crea diferentes problemas.<\/p>\n\n\n\n<h3 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-medium-font-size wp-elements-12\">Si U<sub>c<\/sub> es demasiado bajo<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">Un varistor de \u00f3xido met\u00e1lico es dependiente del voltaje. La operaci\u00f3n repetida o sostenida demasiado cerca de su l\u00edmite continuo puede aumentar la fuga, la temperatura y el envejecimiento. Un sobrevoltaje temporal fuera de la capacidad declarada puede hacer que el desconector t\u00e9rmico interno funcione, dejando el circuito aguas abajo energizado pero ya no protegido contra sobretensiones. En un desajuste severo, la falla puede ser insegura a menos que el producto y la protecci\u00f3n de respaldo lo despejen correctamente.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Un indicador rojo poco despu\u00e9s de la puesta en marcha no prueba necesariamente que el sitio haya experimentado un evento excepcional de rayos. La investigaci\u00f3n debe incluir voltaje en estado estable, integridad del neutro, cableado, exposici\u00f3n a TOV, protecci\u00f3n de respaldo y si el U instalado<sub>c<\/sub> y el circuito coinciden con la red.<\/p>\n\n\n\n<h3 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-medium-font-size wp-elements-13\">Si U<sub>c<\/sub> es demasiado alto<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">Un U m\u00e1s alto<sub>c<\/sub> el varistor normalmente comienza a conducir significativamente a un voltaje m\u00e1s alto. Dependiendo del dise\u00f1o del producto, esto puede aumentar U<sub>p<\/sub>. Por ejemplo, la familia de un fabricante de tipo 2 de un solo polo, comparable en otros aspectos, declara U<sub>p<\/sub> en no m\u00e1s de 1.5 kV para sus versiones de 275 V y 320 V, pero no m\u00e1s de 1.75 kV para su versi\u00f3n de 385 V. Ese es un ejemplo de producto, no una regla de conversi\u00f3n universal, pero muestra por qu\u00e9 el n\u00famero m\u00e1s alto no es autom\u00e1ticamente superior.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">La protecci\u00f3n relevante en la carga no es solo el cat\u00e1logo U<sub>p<\/sub>. La inductancia del cable de conexi\u00f3n a\u00f1ade voltaje mientras la corriente de sobretensi\u00f3n aumenta. Los conductores largos pueden borrar la aparente ventaja de un U m\u00e1s bajo.<sub>p<\/sub>. U<sub>c<\/sub>, U<sub>p<\/sub>, la longitud del conductor y el voltaje de impulso de resistencia del equipo deben coordinarse juntos.<\/p>\n\n\n\n<blockquote class=\"wp-block-quote jutrion-info-box is-layout-flow wp-block-quote-is-layout-flow\">\n<p class=\"wp-block-paragraph\"><strong>Principio de selecci\u00f3n:<\/strong> elegir la clase U m\u00e1s baja<sub>c<\/sub> que est\u00e9 aprobada para el voltaje continuo m\u00e1ximo, modo de protecci\u00f3n, disposici\u00f3n de puesta a tierra y deber de TOV. Luego, confirmar que su U<sub>p<\/sub> y el voltaje del cable instalado permanezcan por debajo del requisito de resistencia al impulso del equipo protegido con un margen adecuado.<\/p>\n<\/blockquote>\n\n\n\n<figure class=\"wp-block-image size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"1024\" height=\"341\" src=\"https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/03-spd-uc-tov-up-selection-tradeoff-1024x341.webp\" alt=\"\" class=\"wp-image-2235\" srcset=\"https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/03-spd-uc-tov-up-selection-tradeoff-1024x341.webp 1024w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/03-spd-uc-tov-up-selection-tradeoff-300x100.webp 300w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/03-spd-uc-tov-up-selection-tradeoff-768x256.webp 768w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/03-spd-uc-tov-up-selection-tradeoff-18x6.webp 18w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/03-spd-uc-tov-up-selection-tradeoff.webp 1200w\" sizes=\"auto, (max-width: 1024px) 100vw, 1024px\" \/><figcaption class=\"wp-element-caption\"><code><em>Compensaci\u00f3n en la selecci\u00f3n de Uc de SPD entre envejecimiento de baja tensi\u00f3n y un nivel de protecci\u00f3n de voltaje m\u00e1s alto a monte.<\/em><\/code><\/figcaption><\/figure>\n\n\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<h2 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-large-font-size wp-elements-14\">Caso de campo: Por qu\u00e9 pasar directamente a 385 V dej\u00f3 expuestos a los VFD<\/h2>\n<\/blockquote>\n\n\n\n<p class=\"wp-block-paragraph\">Una instalaci\u00f3n de envasado de cadena de fr\u00edo anonimizada en el sudeste asi\u00e1tico experiment\u00f3 repetidas operaciones del desconector de SPD en paneles de distribuci\u00f3n secundarios de 230\/400 V durante los primeros tres meses despu\u00e9s de la puesta en marcha. Los indicadores en varios cartuchos de tipo 2 de 275 V cambiaron a rojo. El contratista local asumi\u00f3 que las frecuentes sobretensiones por rayos estaban agotando los SPDs y reemplaz\u00f3 los cartuchos por versiones de 385 V, tratando el U m\u00e1s alto<sub>c<\/sub> como una clasificaci\u00f3n de mayor resistencia.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Dos meses despu\u00e9s, un evento de conmutaci\u00f3n de red fue seguido por una falla diel\u00e9ctrica en tres variadores de frecuencia y dos tarjetas de controlador digital. Los cartuchos de 385 V permanecieron en servicio, obligando a la investigaci\u00f3n a separar la desconexi\u00f3n original por molestias de la posterior falla de coordinaci\u00f3n de protecci\u00f3n.<\/p>\n\n\n\n<figure class=\"wp-block-image size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"1024\" height=\"341\" src=\"https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/04-385v-spd-vfd-field-case-1024x341.webp\" alt=\"\" class=\"wp-image-2233\" srcset=\"https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/04-385v-spd-vfd-field-case-1024x341.webp 1024w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/04-385v-spd-vfd-field-case-300x100.webp 300w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/04-385v-spd-vfd-field-case-768x256.webp 768w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/04-385v-spd-vfd-field-case-18x6.webp 18w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/04-385v-spd-vfd-field-case.webp 1200w\" sizes=\"auto, (max-width: 1024px) 100vw, 1024px\" \/><figcaption class=\"wp-element-caption\"><code><em>Caso de campo mostrando un SPD de 385 V, camino de conexi\u00f3n de 60 cm y aproximadamente 2.4 kV alcanzando los VFD a monte.<\/em><\/code><\/figcaption><\/figure>\n\n\n\n<h3 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-medium-font-size wp-elements-15\">Por qu\u00e9 los cartuchos de 275 V se estaban desconectando<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">El voltaje fase a neutro registrado alcanz\u00f3 repetidamente 258\u2013262 V AC RMS y conten\u00eda una notable distorsi\u00f3n de quinta arm\u00f3nica. La investigaci\u00f3n atribuy\u00f3 el aumento de la fuga y la temperatura del varistor al estr\u00e9s prolongado de la frecuencia de potencia en lugar de a impulsos de rayos repetidos. Esto no significa que cada SPD de 275 V fallar\u00e1 a 262 V: la respuesta tambi\u00e9n depende de los datos de TOV, la forma de onda, la temperatura ambiente y el envejecimiento. Aqu\u00ed, las mediciones del sitio y los datos del producto no se hab\u00edan revisado juntos.<\/p>\n\n\n\n<h3 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-medium-font-size wp-elements-16\">Por qu\u00e9 el reemplazo de 385 V no fue una actualizaci\u00f3n equivalente<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">Los cartuchos de 385 V toleraron el suministro elevado, pero su U<sub>p<\/sub> era de 1.8 kV frente a no m\u00e1s de 1.35 kV para los cartuchos originales. Se estim\u00f3 que la ruta de conexi\u00f3n de 60 cm, para la corriente de sobretensi\u00f3n evaluada y la geometr\u00eda, a\u00f1ad\u00eda aproximadamente 0.6 kV. La estimaci\u00f3n inicial resultante de 2.4 kV no super\u00f3 la resistencia a impulsos de 2.5 kV declarada por los drives, pero dejaba casi ning\u00fan margen para tolerancia, forma de onda y efectos de instalaci\u00f3n.<\/p>\n\n\n\n<h3 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-medium-font-size wp-elements-17\">Resoluci\u00f3n: Utilizar la Clase de Media Tensi\u00f3n y Acortar la Ruta de Corriente<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">El reemplazo utiliz\u00f3 una configuraci\u00f3n JUTRION de 320 V Tipo 2 declarada en U<sub>p<\/sub> \u2264 1.4 kV. Su U<sub>c<\/sub> proporcion\u00f3 aproximadamente 22% de margen sobre los 262 V RMS registrados, sujeto a confirmaci\u00f3n contra la documentaci\u00f3n del producto y la evaluaci\u00f3n de TOV del sitio. Las conexiones de barra colectora y el cableado V optimizado redujeron la ruta total de aproximadamente 60 cm a menos de 25 cm; bajo el mismo m\u00e9todo de estimaci\u00f3n, la adici\u00f3n inductiva cay\u00f3 por debajo de aproximadamente 0.25 kV y la estimaci\u00f3n de protecci\u00f3n efectiva se mantuvo por debajo de aproximadamente 1.65 kV.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">No se reportaron desconexiones molestas repetidas ni da\u00f1os relacionados en el controlador durante el per\u00edodo de observaci\u00f3n. La correcci\u00f3n combin\u00f3 un margen de voltaje continuo suficiente, un U<sub>p<\/sub> m\u00e1s bajo y una ruta de descarga m\u00e1s corta en lugar de seleccionar autom\u00e1ticamente el U<sub>c<\/sub>.<\/p>\n\n\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<h2 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-large-font-size wp-elements-18\">m\u00e1s alto.<\/h2>\n<\/blockquote>\n\n\n\n<p class=\"wp-block-paragraph\">Una Comparaci\u00f3n de Panel de 230\/400 V<\/p>\n\n\n\n<ol class=\"wp-block-list\">\n<li><strong>Para un tablero comercial ilustrativo de 230\/400 V con conductores N y PE separados y un SPD 3+1, revise los candidatos en este orden:.<\/strong> Identifique el voltaje de modo.<\/li>\n\n\n\n<li><strong>Cada m\u00f3dulo de fase est\u00e1 conectado L\u2013N, por lo que normalmente ve alrededor de 230 V, no 400 V.<\/strong> Establezca el voltaje de suministro continuo m\u00e1s alto.<\/li>\n\n\n\n<li><strong>Utilice la tolerancia de suministro del proyecto y cualquier dato verificado del sitio. No trate una condici\u00f3n anormal de neutro como un punto de operaci\u00f3n continuo ordinario.<\/strong> Defina el deber de TOV.<sub>T<\/sub>Revise el sistema de puesta a tierra, fallos plausibles de neutro y tierra, y los datos de U.<\/li>\n\n\n\n<li><strong>frente al tiempo requeridos por el dise\u00f1o de instalaci\u00f3n.<\/strong> Compare productos aprobados.<\/li>\n\n\n\n<li><strong>Una versi\u00f3n de 275 V puede proporcionar un rendimiento continuo y de TOV adecuado. Si no lo hace, se puede evaluar la versi\u00f3n de 320 V. Una versi\u00f3n de 385 V sigue siendo un candidato solo si el margen m\u00e1s alto es realmente necesario.<\/strong> Verifique nuevamente el rendimiento de protecci\u00f3n.<sub>p<\/sub> Compare U.<\/li>\n<\/ol>\n\n\n\n<figure class=\"wp-block-image size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"1024\" height=\"341\" src=\"https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/05-spd-lead-length-v-wiring-comparison-1024x341.webp\" alt=\"\" class=\"wp-image-2234\" srcset=\"https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/05-spd-lead-length-v-wiring-comparison-1024x341.webp 1024w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/05-spd-lead-length-v-wiring-comparison-300x100.webp 300w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/05-spd-lead-length-v-wiring-comparison-768x256.webp 768w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/05-spd-lead-length-v-wiring-comparison-18x6.webp 18w, https:\/\/jutrion.com\/wp-content\/uploads\/2026\/10\/05-spd-lead-length-v-wiring-comparison.webp 1200w\" sizes=\"auto, (max-width: 1024px) 100vw, 1024px\" \/><figcaption class=\"wp-element-caption\"><code>para cada modelo exacto, luego incluya el efecto de los conductores de conexi\u00f3n y la coordinaci\u00f3n con la protecci\u00f3n aguas abajo.<\/code><\/figcaption><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\"><em>Comparaci\u00f3n de una conexi\u00f3n SPD de 60 cm y cableado V optimizado por debajo de 25 cm para mejorar la protecci\u00f3n VFD.<\/em><sub>p<\/sub> Si 275 V pasa las verificaciones de voltaje continuo y TOV, normalmente sigue siendo el primer candidato. Pase a 320 V cuando se requiera margen adicional y U.<\/p>\n\n\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<h2 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-large-font-size wp-elements-19\">siga siendo aceptable. Utilice 385 V solo cuando el modo o el deber de TOV lo justifique y el c\u00e1lculo de protecci\u00f3n aguas abajo a\u00fan pase.<sub>c<\/sub>, U<sub>T<\/sub> Lea U<sub>p<\/sub> y U<\/h2>\n<\/blockquote>\n\n\n\n<p class=\"wp-block-paragraph\">como Un Conjunto<\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li><strong>U<sub>c<\/sub>:<\/strong> \u00bfQu\u00e9 voltaje puede permanecer continuamente en este modo de protecci\u00f3n?<\/li>\n\n\n\n<li><strong>U<sub>T<\/sub> o caracter\u00edstica TOV:<\/strong> \u00bfQu\u00e9 sucede ante un sobrevoltaje de frecuencia de potencia declarado y duraci\u00f3n\u2014\u00bfsoporta el SPD o falla de manera segura?<\/li>\n\n\n\n<li><strong>U<sub>p<\/sub>:<\/strong> \u00bfA qu\u00e9 nivel declarado limita el SPD un impulso especificado en sus terminales?<\/li>\n<\/ul>\n\n\n\n<p class=\"wp-block-paragraph\">No infieras un valor de otro. Despu\u00e9s de establecer la compatibilidad de voltaje, verifica por separado el tipo 1, tipo 2 o tipo 1+2; I<sub>imp<\/sub>, yo<sub>n<\/sub> e I<sub>m\u00e1x<\/sub>; corriente de cortocircuito prospectiva; desconexi\u00f3n; protecci\u00f3n de respaldo; e indicaci\u00f3n remota.<\/p>\n\n\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<h2 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-large-font-size wp-elements-20\">Qu\u00e9 incluir en una consulta o especificaci\u00f3n de SPD<\/h2>\n<\/blockquote>\n\n\n\n<p class=\"wp-block-paragraph\">\u201cNecesito un SPD 4P 385 V\u201d no es suficiente informaci\u00f3n para una coincidencia de producto confiable. Env\u00eda el contexto el\u00e9ctrico que determina el deber del cartucho:<\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li>voltaje y frecuencia nominal del sistema;<\/li>\n\n\n\n<li>disposici\u00f3n de conductores monof\u00e1sicos o trif\u00e1sicos;<\/li>\n\n\n\n<li>sistema de puesta a tierra: TN-C, TN-S, TT, IT u otra disposici\u00f3n definida;<\/li>\n\n\n\n<li>circuito de protecci\u00f3n requerido, como 1+1, 3+1 o 4+0;<\/li>\n\n\n\n<li>tipo de SPD y posici\u00f3n de instalaci\u00f3n;<\/li>\n\n\n\n<li>U requerida<sub>c<\/sub>, TOV y U<sub>p<\/sub> rendimiento;<\/li>\n\n\n\n<li>I<sub>imp<\/sub>, yo<sub>n<\/sub> e I<sub>m\u00e1x<\/sub> requisitos;<\/li>\n\n\n\n<li>corriente de cortocircuito prospectiva y protecci\u00f3n aguas arriba;<\/li>\n\n\n\n<li>contacto remoto, m\u00f3dulo reemplazable y requisitos de certificaci\u00f3n; y<\/li>\n\n\n\n<li>mercado de destino, cantidad y necesidades de documentaci\u00f3n del proyecto.<\/li>\n<\/ul>\n\n\n\n<p class=\"wp-block-paragraph\">La <a href=\"https:\/\/jutrion.com\/es\/spd\/\">Rango de SPD AC de JUTRION<\/a> incluye opciones de tipo 2 y tipo 1+2 para sistemas de distribuci\u00f3n de baja tensi\u00f3n. Un modelo final debe coincidir con la red real y el diagrama de conexi\u00f3n en lugar de seleccionarse del n\u00famero U<sub>c<\/sub> de forma aislada.<\/p>\n\n\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<h2 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-large-font-size wp-elements-21\">Preguntas Comunes Sobre SPDs de 275 V, 320 V y 385 V<\/h2>\n<\/blockquote>\n\n\n<div id=\"rank-math-faq\" class=\"rank-math-block\">\n<div class=\"rank-math-list\">\n<div id=\"faq-question-1791463372687\" class=\"rank-math-list-item\">\n<h3 class=\"rank-math-question\">\u00bfPuedo usar un SPD de 385 V en un sistema de 230 V?<\/h3>\n<div class=\"rank-math-answer\">\n\n<p>Posiblemente, pero no es autom\u00e1ticamente la mejor opci\u00f3n. Confirma que el producto est\u00e9 declarado para la red y el modo de protecci\u00f3n, luego compara su U<sub>p<\/sub> con el equipo protegido. El margen adicional de U<sub>c<\/sub> es \u00fatil solo si el dise\u00f1o lo necesita y el nivel de protecci\u00f3n resultante sigue siendo aceptable.<\/p>\n\n<\/div>\n<\/div>\n<div id=\"faq-question-1791464255661\" class=\"rank-math-list-item\">\n<h3 class=\"rank-math-question\">\u00bfEs un SPD de 275 V siempre correcto para un suministro de 230 V?<\/h3>\n<div class=\"rank-math-answer\">\n\n<p>No. Es un candidato com\u00fan para un modo que normalmente ve 230 V, pero la idoneidad depende del voltaje continuo m\u00e1ximo, el sistema de puesta a tierra, la exposici\u00f3n a TOV, la disposici\u00f3n del circuito y la hoja de datos exacta.<\/p>\n\n<\/div>\n<\/div>\n<div id=\"faq-question-1791464321354\" class=\"rank-math-list-item\">\n<h3 class=\"rank-math-question\">\u00bfPor qu\u00e9 fallar\u00eda un SPD cuando no se report\u00f3 un rayo?<\/h3>\n<div class=\"rank-math-answer\">\n\n<p>Las causas posibles incluyen sobretensiones por conmutaci\u00f3n repetida, sobrevoltaje sostenido, un neutro perdido o inestable, U<sub>c<\/sub>, incorrecto, circuito de protecci\u00f3n incorrecto, envejecimiento, conexiones sueltas o coordinaci\u00f3n de respaldo inadecuada. Un indicador fallido es una raz\u00f3n para investigar el sistema, no simplemente para instalar un cartucho de mayor voltaje.<\/p>\n\n<\/div>\n<\/div>\n<div id=\"faq-question-1791464332925\" class=\"rank-math-list-item\">\n<h3 class=\"rank-math-question\">\u00bfSignifica U de 320 V un sistema nominal de 320 V?<sub>c<\/sub> No. U<\/h3>\n<div class=\"rank-math-answer\">\n\n<p>es el voltaje continuo m\u00e1ximo en el modo de protecci\u00f3n del SPD, no necesariamente la designaci\u00f3n del sistema l\u00ednea a l\u00ednea o l\u00ednea a neutro nominal. L\u00e9elo con el diagrama de conexi\u00f3n.<sub>c<\/sub> \u00bfSon intercambiables U.<\/p>\n\n<\/div>\n<\/div>\n<div id=\"faq-question-1791464348648\" class=\"rank-math-list-item\">\n<h3 class=\"rank-math-question\">?<sub>c<\/sub> Lea U<sub>CPV<\/sub> se utiliza para aplicaciones de SPD DC fotovoltaico y debe seleccionarse del voltaje m\u00e1ximo de cadena PV bajo las condiciones de temperatura del proyecto. Para esa tarea, utiliza la gu\u00eda de selecci\u00f3n de SPD DC separada para solar PV.<\/h3>\n<div class=\"rank-math-answer\">\n\n<p>es el voltaje continuo m\u00e1ximo en el modo de protecci\u00f3n del SPD, no necesariamente la designaci\u00f3n del sistema l\u00ednea a l\u00ednea o l\u00ednea a neutro nominal. L\u00e9elo con el diagrama de conexi\u00f3n.<sub>CPV<\/sub> La Regla de Selecci\u00f3n Pr\u00e1ctica <a href=\"https:\/\/jutrion.com\/es\/how-to-select-dc-spd-solar-pv\/\">Gu\u00eda de selecci\u00f3n de SPD de CC para PV solar<\/a>.<\/p>\n\n<\/div>\n<\/div>\n<\/div>\n<\/div>\n\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<h2 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-large-font-size wp-elements-22\">La regla pr\u00e1ctica de selecci\u00f3n<\/h2>\n<\/blockquote>\n\n\n\n<p class=\"wp-block-paragraph\">No elija 275 V, 320 V o 385 V de la etiqueta frontal del cuadro de distribuci\u00f3n. Primero establezca el voltaje en cada modo de protecci\u00f3n de SPD, luego verifique el voltaje continuo m\u00e1s alto, la disposici\u00f3n de puesta a tierra y el servicio TOV. De las clasificaciones que superen esas verificaciones, elija la opci\u00f3n que a\u00fan brinde una coordinaci\u00f3n U adecuada en el equipo protegido.<sub>p<\/sub> En muchos modos de protecci\u00f3n ordinarios de 230 V, ese proceso comienza con 275 V. Pasa a 320 V o 385 V solo cuando las condiciones de la red y los datos del fabricante respaldan el cambio. Un U m\u00e1s alto es un margen de voltaje adicional, no una medida universal de mejor protecci\u00f3n contra sobretensiones.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">IEC 61643-11:2025 \u2014 Dispositivos de protecci\u00f3n contra sobretensiones de baja tensi\u00f3n conectados a sistemas de energ\u00eda de baja tensi\u00f3n de CA<sub>c<\/sub> IEC 61643-12:2020 \u2014 Principios de selecci\u00f3n y aplicaci\u00f3n para SPDs de baja tensi\u00f3n.<\/p>\n\n\n\n<h3 class=\"wp-block-heading has-palette-color-9-color has-text-color has-link-color has-medium-font-size wp-elements-23\">Referencias T\u00e9cnicas<\/h3>\n\n\n\n<ul class=\"wp-block-list\">\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/65314\" target=\"_blank\" rel=\"noopener\">Schneider Electric \u2014 Par\u00e1metros de SPD IEC incluyendo U<\/a><\/li>\n\n\n\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/32531\" target=\"_blank\" rel=\"noopener\">IEC 61643-12:2020 \u2014 Principios de selecci\u00f3n y aplicaci\u00f3n para SPD de baja tensi\u00f3n<\/a><\/li>\n\n\n\n<li><a href=\"https:\/\/www.se.com\/ar\/es\/faqs\/FAQ000246782\/\" target=\"_blank\" rel=\"noopener\">Schneider Electric \u2014 Par\u00e1metros de SPD de IEC incluyendo U<sub>c<\/sub>, U<sub>p<\/sub> e I<sub>n<\/sub><\/a><\/li>\n<\/ul>","protected":false},"excerpt":{"rendered":"<p>275 V, 320 V or 385 V: The Short Answer For a 230\/400 V AC installation, a 275 V SPD is often the first candidate when its protection mode normally sees about 230 V, but it is not an automatic choice for every network. Use 320 V when the approved design needs more continuous-voltage or [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":2236,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[1],"tags":[],"class_list":["post-2209","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-electrical-guides"],"blocksy_meta":[],"_links":{"self":[{"href":"https:\/\/jutrion.com\/es\/wp-json\/wp\/v2\/posts\/2209","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/jutrion.com\/es\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/jutrion.com\/es\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/jutrion.com\/es\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/jutrion.com\/es\/wp-json\/wp\/v2\/comments?post=2209"}],"version-history":[{"count":1,"href":"https:\/\/jutrion.com\/es\/wp-json\/wp\/v2\/posts\/2209\/revisions"}],"predecessor-version":[{"id":2237,"href":"https:\/\/jutrion.com\/es\/wp-json\/wp\/v2\/posts\/2209\/revisions\/2237"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/jutrion.com\/es\/wp-json\/wp\/v2\/media\/2236"}],"wp:attachment":[{"href":"https:\/\/jutrion.com\/es\/wp-json\/wp\/v2\/media?parent=2209"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/jutrion.com\/es\/wp-json\/wp\/v2\/categories?post=2209"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/jutrion.com\/es\/wp-json\/wp\/v2\/tags?post=2209"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}