โซลาร์และดีซี
PV SPD Minimum Uซีพีวี เครื่องคำนวณ
Derive the minimum continuous operating voltage Uซีพีวี a PV surge protective device must have, from the string open-circuit voltage corrected for cold temperature, and screen the SPD type and connection. Under-rating Uซีพีวี lets the array voltage age or fail the SPD; over-rating weakens the protection level.
How Uซีพีวี is derived
Uซีพีวี is the maximum continuous DC voltage the SPD withstands without conducting. It must sit above the highest voltage the array ever presents — the cold open-circuit voltage — with a 1.1 margin so the SPD is not stressed in normal service. The 1.2 × Voc,STC rule of thumb is a quick equivalent that folds temperature and margin into one factor; use the higher of the two results.
Type and connection
- ประเภท 2 — the usual choice, protecting the array and inverter from induced and switching surges where there is no external lightning protection system.
- Type 1 (or 1+2) — required where the building has an external LPS or high direct-strike exposure, to handle partial lightning current.
PV SPDs commonly use a Y (3+0) connection — each DC pole to earth through a varistor plus a spark gap between the mid-point and earth — so a single earth fault does not defeat the protection. Follow the SPD maker’s wiring for the array earthing arrangement.
คำถามที่พบบ่อย
Why not just use Voc at STC?
Because the array voltage rises in the cold and the SPD needs headroom above the worst case. Sizing Uซีพีวี on the STC value risks continuous stress and premature ageing on cold, sunny days.
Where do PV SPDs go?
At the array/combiner and at the inverter DC input, with a second device where cable runs exceed roughly 10 m. Both AC and DC sides of a PV system need their own SPDs.
Type 1 or Type 2 for my site?
Type 2 without an external lightning protection system; Type 1 (or a combined Type 1+2) where an LPS is present or the exposure is high. The Uซีพีวี requirement is identical for both.
Select the PV SPD
Match the Uซีพีวี, type, and connection to a DC surge protective device for the array and inverter.
Estimate for guidance only. The final Uซีพีวี, SPD type, connection, and positions must be confirmed by a qualified person against IEC 61643-31, the array design, and the site lightning risk.