Motor & switching

Motor Overload Relay Setting Calculator

Turn the motor nameplate current, service factor, and starting duty into a preliminary thermal-overload dial setting and trip class for a contactor-mounted overload relay. The nameplate current governs — these are starting points to be trimmed on commissioning.

Recommended dial setting
A
Setting range
Trip class
Guidance

Setting: dial to the motor, not the cable

A thermal overload relay protects the motor windings, so it is set from the motor’s actual full-load current, taken from the nameplate. The service factor sets the allowable margin above it:

Service factor 1.0 : set ≈ 100–115 % of FLC Service factor 1.15+ : set ≈ 115–125 % of FLC

Start at the FLC on the dial and trim upward within the range only if the motor nuisance-trips at a genuinely acceptable load. Setting above the range removes winding protection; setting far below it causes nuisance trips.

Trip class: match the start time

ClassTrip time at 7.2 × settingUse
Class 10≤ 10 sNormal starting — pumps, fans, standard loads
Class 20≤ 20 sHeavy starting — loaded conveyors, mixers
Class 30≤ 30 sVery heavy / high-inertia — crushers, centrifuges

The class must let the motor accelerate without tripping, yet still protect the windings during a stalled or locked-rotor condition. A long-starting motor on a Class 10 relay trips on every start; too high a class on a quick-starting motor slows protection.

Temperature compensation matters. A non-compensated bimetallic relay shifts its trip point with its own ambient. Where the relay sits in a hot enclosure or a different ambient from the motor, use a temperature-compensated relay or apply the manufacturer’s correction.

Frequently asked questions

Do I use the nameplate current or the cable rating?

Always the motor nameplate FLC. The overload protects the motor; the cable and short-circuit protection are handled separately by the breaker or fuse.

My motor trips during start — raise the setting?

Usually no. First check the trip class matches the start time — a heavy or high-inertia load often needs Class 20 or 30. Only trim the current setting within its range, and never above the service-factor limit.

Electronic overload or bimetallic?

Electronic overloads offer wider setting ranges, selectable classes, phase-loss and phase-imbalance protection, and better temperature stability. Bimetallic relays are simple and economical for standard duties.

Build the starter

Pair the overload relay with a correctly rated AC contactor and short-circuit protection for a complete motor starter.

Standards referencedIEC 60947-4-1 (contactors & motor-starters, overload relays & trip classes) · motor nameplate data.

Preliminary setting for guidance only. The final overload setting and trip class must be confirmed by a qualified person against the motor nameplate, the driven load, and the relay manufacturer’s data, then verified on commissioning.