Circuit protection

RCCB & RCBO Selector (Type & IΔn)

Turn the load waveform, protection purpose, and expected standing leakage into a preliminary residual-current requirement: RCD type (AC, A, F or B), rated sensitivity IΔn, and whether an RCCB with a separate MCB or an all-in-one RCBO fits the circuit. A design starting point — the mandatory type and sensitivity follow the national wiring rules.

RCD type
Rated sensitivity IΔn
Device
Unwanted-tripping check (IΔn ≥ 3 × leakage)

Type: match the waveform, not just the load

An RCD only detects the residual-current shapes it is built for. Fit a type that cannot see the earth fault and the protection is defeated, so the waveform the load can produce governs the choice.

TypeDetectsTypical circuits
ACSinusoidal AC residual currentLegacy resistive loads. Not permitted for general use in many regions.
AAC + pulsating DCThe common default — sockets, lighting, single-phase electronics.
FType A + mixed frequenciesSingle-phase VFDs, washing machines, some IT loads.
BType F + smooth DCThree-phase VFDs, EV chargers, PV inverters.

Sensitivity: what IΔn is for

  • 30 mA — additional protection for people. Required for most socket circuits and wet locations.
  • 100–300 mA — fire protection on feeders and installations.
  • ≤ 500 mA — fault protection / disconnection where personal-shock protection is provided elsewhere.

Standing (healthy) leakage from filters and long cables must stay well below the trip threshold. IEC 60364 guidance keeps the total steady leakage under about one third of IΔn, so the working rule is:

IΔn ≥ 3 × standing leakage current

If several circuits share one RCD, their leakage adds up — split the load across more RCDs, or use a lower-leakage arrangement, rather than raising IΔn past the level required for protection.

Type and sensitivity are code-driven. Whether a 30 mA RCD is mandatory, and which type, is set by the adopted wiring standard (IEC 60364-4-41, BS 7671, or local rules) and the equipment. Confirm the requirement for the destination before finalising.

RCCB or RCBO?

An RCCB provides residual-current protection only and needs an upstream MCB for overload and short-circuit protection. An RCBO combines both in one module, isolates the affected circuit alone, and suits per-circuit protection in a modern board. Choose the RCBO when board space and per-circuit selectivity matter; choose an RCCB + MCB to protect a group of final circuits together.

Frequently asked questions

Can I still use a Type AC RCD?

Many wiring standards no longer allow Type AC for general circuits because modern electronic loads produce pulsating DC residual currents it cannot detect. Type A is the usual minimum. Check the current edition adopted for the project.

Why does my RCD trip with nothing obviously wrong?

Cumulative standing leakage from electronics and long cables can approach the threshold. Keep IΔn ≥ 3 × the total leakage and split circuits across more RCDs instead of raising the sensitivity.

Do EV chargers need a Type B RCD?

EV and three-phase drive circuits can produce smooth DC residual current that blinds Type A/F. A Type B RCD, or a charger with built-in DC fault detection plus Type A, is used — follow the equipment instructions and local rules.

Select the RCD

With the type, sensitivity, and pole count set, match a residual-current device to the circuit and market.

Standards referencedIEC 61008 (RCCB) · IEC 61009 (RCBO) · IEC 62423 (Type F & B) · IEC 60364-4-41 (additional protection, disconnection).

Preliminary guidance only. The mandatory RCD type, sensitivity, and arrangement must be confirmed by a qualified person against the adopted wiring standard, the equipment, and the site leakage.